Monthly functional testing and annual full-duration testing, with logbook management, remedials handled in the same visit, and records that stand up when a fire officer asks to see them.

at a glance

What is emergency lighting testing?

Emergency lighting testing is the routine checking of the lighting that illuminates escape routes when the normal power supply fails. It has two parts: a brief monthly functional test that each luminaire illuminates, and an annual test that runs the system for its full rated duration to prove the batteries still hold enough charge to see people out of the building.

The two tests find different faults, which is why doing one is not a substitute for the other. The monthly test finds dead lamps and failed drivers. The annual duration test finds dying batteries, and batteries fail gradually rather than suddenly. A luminaire that lights up perfectly during a monthly check may go dark after twenty minutes, which is precisely when people would still be in the building.

That is the failure mode nobody sees until it matters. Plenty of buildings run the monthly checks diligently for years and skip the annual duration test because it takes three hours and leaves the system discharged afterwards. Those buildings have a logbook full of passes and an emergency lighting system that would not complete an evacuation.

Where emergency lighting is required

Coverage is set at design stage against the escape routes as they were then. It is worth re-checking whenever a building is partitioned, extended or has its circulation changed.

How we test emergency lighting

We test coverage as well as function. Confirming that the fittings which exist still work is only half the job if the escape routes have changed since they were installed.

Every luminaire recorded individually

Results are logged per fitting, not as a building-level pass. That is what makes a failure traceable and a logbook defensible, and it is the difference between knowing you have a problem and knowing where it is.

Coverage checked against current escape routes

We record what is actually installed against the escape routes as they are now. Partitioning, new plant rooms and changed circulation routinely leave sections of a route unlit, and no functional test will ever reveal that.

Duration tests planned around occupancy

Annual tests are normally run overnight or at a weekend so the building is unoccupied while the system discharges and recharges. On large sites we test by zone across several visits so the whole building is never simultaneously at reduced duration.

Remedials in the same visit

Lamps, batteries and complete luminaires replaced while we are on site wherever stock allows, rather than a return visit and a second mobilisation charge.

Logbook completed, not just certificates issued

The logbook is the record a fire officer asks to see. We complete it on site and issue digital certification alongside, so the paper record and the digital one agree.

Automatic test systems supported

Where self-testing luminaires or a central addressable system are installed we work with them rather than around them, using their reporting and verifying it rather than duplicating the whole exercise manually.

What is included, step by step

Stage 01

Asset survey

Every luminaire and exit sign located and recorded, with type, position and rated duration. On sites with no existing record this is where the programme actually begins.

Stage 02

Coverage review

Installed fittings checked against current escape routes and final exits, with any gaps from building changes flagged before testing starts.

Stage 03

Monthly functional testing

Short interruption of the normal supply, each luminaire confirmed to illuminate, results recorded per fitting. Can be run by us or left with your team.

Stage 04

Annual duration test

Full rated duration, normally three hours, scheduled outside occupancy. Any fitting failing before the end is identified and its battery replaced.

Stage 05

Remedials

Failed lamps, batteries and luminaires replaced, and any coverage gaps quoted with a recommendation rather than simply noted.

Stage 06

Certification and logbook

Digital certification issued and the on-site logbook completed, with the next test date tracked so nothing lapses by accident.

Who needs emergency lighting testing

Effectively every non-domestic building with an escape route that would be unsafe in darkness. What changes between building types is the rated duration required, the type of fittings and how disruptive the annual test is to arrange.

Offices and multi-tenant buildings

Usually non-maintained fittings on a three-hour duration, with the complication that responsibility for common parts and demised areas is split between landlord and tenants. Worth settling in writing before a programme starts.

Care homes and premises where people sleep

The highest stakes and the least tolerance for a failed duration test, because evacuation is slow and assisted. Three-hour duration is standard and testing has to be planned with extreme care around residents.

Schools, colleges and academies

Large sites, long escape routes and holiday periods that make annual duration testing straightforward to schedule. Coverage changes frequently as classrooms are reconfigured.

Warehousing and industrial

High bays, long escape distances and racking that is regularly reconfigured, which moves escape routes without anyone treating it as a lighting change. Coverage review matters more here than almost anywhere.

Retail, hospitality and places of assembly

Frequently need maintained fittings because lighting is dimmed while the premises are occupied. Testing is scheduled outside trading, which in hospitality means genuinely awkward hours.

Emergency lighting: common questions

BS 5266-1 requires a short functional test every month and a full rated-duration test every year, with every result recorded. The monthly test confirms each luminaire illuminates when the normal supply is interrupted. The annual test runs the system for its full rated duration, normally three hours, to prove the batteries will last as long as the design intends.

The system is put into emergency mode and left running until its rated duration expires, normally three hours. Any luminaire that fails before the end has a battery at end of life. It is the only test that proves the system would work in a real evacuation, because a monthly functional test tells you a lamp illuminates but nothing about whether it would still be lit twenty minutes into an incident.

The responsible person under the Regulatory Reform (Fire Safety) Order 2005, which in most commercial buildings in England and Wales is the employer, owner or occupier. Scotland and Northern Ireland have equivalent duties under their own fire safety legislation. The duty includes keeping records, which is why an up-to-date logbook matters as much as the testing itself.

A maintained luminaire is lit continuously, both on normal supply and on battery. A non-maintained luminaire only illuminates when the normal supply fails. Maintained fittings are usual in places of assembly, cinemas and premises where lighting may be dimmed while occupied. Non-maintained is common in offices and industrial buildings.

BS 5266-1 sets a minimum of 1 lux along the centre line of a defined escape route, 0.5 lux in open anti-panic areas, and for high risk task areas 10 percent of the normal illuminance or 15 lux, whichever is greater. Those are minimum maintained values at the end of the rated duration, not readings taken when the batteries are fresh.

Yes, and many sites do. Where a test key switch or an automatic test system is installed the monthly check is straightforward. The annual duration test and the certification are usually better outsourced, because the records need to be complete and defensible. We are happy to run the annual test and leave the monthly checks with your team, with the logbook set up so the two line up.

Quite possibly not. Emergency lighting is designed around escape routes and final exits at a point in time, and new partitioning, plant rooms or changed circulation can leave gaps. We record actual coverage against current escape routes as part of testing and flag anything that no longer works, rather than testing what is there and ignoring what is missing.

After a full duration test the batteries are discharged, and BS 5266-1 expects them to recharge within 24 hours. During that recovery window the system cannot deliver its full rated duration, which is why annual tests are normally done at the start of a period when the building is unoccupied rather than immediately before it fills up.

Why Smartec Energy

Emergency lighting sits between electrical compliance and fire safety, and it is frequently the item that falls between two suppliers. We would rather own it than split it.

Related pages

Commercial solar funding: PPA,hire purchase compared

The three ways to pay for a commercial solar system, with worked examples and tax position for each

Electrical compliance and EICR testing

Fixed wire testing, PAT testing and emergency lighting. Most renewable projects surface remedial work on the existing installation.

Commercial battery storage systems

Store the generation you cannot use as it is produced, sized from a full year of real data.

Book emergency lighting testing

Monthly, annual, or the annual duration test alone if your team handles the monthly checks. Tell us the site and roughly how many fittings and we will propose a schedule that keeps the logbook complete.